Manufacturer: CyberPower
Model:CyberPower Smart App LCD UPS 1500VA 1350W, RM, 2U, 15A, 120V
Condition: New batteries, refurbished UPS
Part Number: OL1500RTXL2U
Maximum output: 1350W/1500VA
Typical backup time at half load: 11 minutes (675 Watts)
Typical backup time at full load: 3.4 minutes (1350 Watts)
Warranty: 1 year full replacement warranty
CyberPower Smart App LCD UPS 1500VA 1350W RM 2U OL1500RTXL2U User\'s Manual
OL1500RTXL2U - CyberPower Smart App LCD UPS 1500VA Specifications:
General:
Energy Saving
Energy Star Certified
Yes
UPS Topology
Online Double Conversion
Battery:
Battery Quantity
3
Battery Size
12 V / 9 Ah
Battery Type
Sealed Lead-Acid Battery
Extended Battery Module
BP36V60ART2U
Hot Swappable
Yes
Replacement Battery Cartridge
RB1290X3L
Replacement Battery Cartridge Quantity
1
Runtime at Full Load
3.4 min
Runtime at Half Load
11 min
Smart Battery Management (SBM) Mode
Yes
Typical Recharge Time
4 Hours (0% to 90% charged)
Input:
Circuit Breaker
15A
Cold Start
Yes
Cord Length
10 ft (3 m)
Input Frequency Range
40 Hz – 70 Hz
Input Plug Type
NEMA 5-15P
Input Power Factor
0.99
Input Voltage Range
60 VAC – 69 VAC for 0–60% Load
70 VAC – 79 VAC for 0–70% Load
80 VAC – 89 VAC for 0–80% Load
90 VAC – 95 VAC for 0–90% Load
96 VAC – 150 VAC for 0–100% Load
Nominal Input Voltage
100 – 125 VAC
Output:
Bypass
Internal Bypass (Automatic and Manual)
Crest Factor
3:1
ECO Mode Voltage Regulation
±10%, ±15% (Configurable)
Harmonic Distortion
< 3% at Linear Load
< 5% at Non-Linear Load
On Battery Frequency
50/60 Hz ± 0.25Hz (auto-sensing or configurable)
On Battery Voltage
100/110/115/120/125 VAC ± 2% (configurable)
On Battery Waveform
Sine Wave
Outlet Type
(8) NEMA 5-15R
Outlets – Total
8
Output Power Factor
0.9
Overload Protection
Line Mode: 105% ~ 125% Load – 1 min
Line Mode: 126% ~ 150% Load – 10 sec
Battery Mode: 105% ~ 130% Load – 10 sec
Battery Mode: 131% – 150% Load – 2 sec
Short Circuit Protection
UPS Output Cut Off Immediately or Input Fuse / Circuit Breaker Protection
Typical Transfer Time
0 ms
VA
1500VA
Watts
1350W
Surge Protection & Filtering:
EMI/RFI Filtration
Yes
Phone / Network Protection RJ11/RJ45
1-In / 1-Out (Combo)
Surge Suppression (Joules)
1780 J
Management & Communications:
Audible Alarms
Battery Mode
Low Battery
Overload
Fault
HID Compliant USB Port
Yes
LCD
Multifunction LCD
LED Indicators
Power On (White)
Line Mode (Green)
Battery Mode (Yellow)
Bypass Mode (Yellow)
Fault (Red)
Replace Battery (Red)
Management Cable
USB Cable
Serial Cable
Removable LCD Control Panel Option
Yes – Requires DB26 cable (not included)
Serial Port
1 Dry Contact
Software (Free Download)
PowerPanel® Business
Physical:
Form Factor
Material of Construction
Metal
Rack Height
2U
Dimensions:
Physical Dimensions – (WxHxD) (cm)
43.18 x 8.89 x 42.93 (cm)
Physical Dimensions – (WxHxD) (in)
17 x 3.5 x 16.9 (in)
Physical Dimensions – (WxHxD) (mm)
432 x 89 x 429 (mm)
Weight (kg)
17.96
Weight (lb)
39.6
![Buy Now Buy Now](buy.gif)