Manufacturer: Tripp Lite
Model: Tripp Lite SmartPro UPS 5000VA 3750W, RM, 30A, 208V Input, 208/120V Output
Condition: New batteries, refurbished UPS
Part Number: SMART5000XFMRXL
Maximum output: 3750W / 5000VA
Typical backup time at half load: 20 minutes (1875 Watts)
Typical backup time at full load: 8.5 minutes (3750 Watts)
Warranty: 1 year full replacement warranty
Tripp Lite SmartPro 5000VA 3750W RM 3U 208/120VSMART5000XFMRXLManual
SMART5000XFMRXL - Tripp Lite SmartPro 5000VASpecifications:
Input:
Rated input current (Maximum Load)
24A
Nominal Input Voltage(s) Supported
208V AC
UPS Input Connection Type
NEMA L6-30P
Input Circuit Breakers
20A
UPS Input Cord Length (ft.)
10
UPS Input Cord Length (m)
3.1
Recommended Electrical Service
30A 208V
Input Phase
Single-Phase
Output:
Output Volt Amp Capacity (VA)
5000
Output kVA Capacity (kVA)
5
Output Watt Capacity (Watts)
3750
Output kW Capacity (kW)
3.75
Power Factor
0.75
Nominal Voltage Details
208/120V nominal output in battery mode
Frequency Compatibility
60 Hz
Output Voltage Regulation (Line Mode)
208 & 120V (+/- 10%)
Output Voltage Regulation (Economy Line Mode)
+/- 10%
Output Voltage Regulation (Battery Mode)
+/- 5%
Load Management Receptacles
Eight switchable single-outlet 5-15/20R load banks
Output Circuit Breakers
20A double pole breaker supports L6-20R outlets, 20A branch rated breaker (x2) supports 4 5-15/20R outlets each, L6-30R outlet is unbreakered
Output AC Waveform (AC Mode)
Sine wave
Output AC Waveform (Battery Mode)
Pure Sine wave
Nominal Output Voltage(s) Supported
110V; 115V; 120V; 208V
Output Receptacles
(8) NEMA 5-15/20R
(2) NEMA L6-20R
(1) NEMA L6-30R
Individually Controllable Load Banks
Yes
Battery:
Full Load Runtime (min.)
8.5 min. (3750w)
Half Load Runtime (min.)
20 min. (1875w)
Expandable Battery Runtime
Extended runtime supported via optional external battery packs
External Battery Pack Compatibility
BP48V27-2US (multi-pack compatible); BP48V60RT-3U (multi-pack compatible)
DC System Voltage (VDC)
48
Battery Recharge Rate (Included Batteries)
6.8 hours from 10% to 90% (typical, full load discharge)
Internal UPS Replacement Battery Cartridge
RBC94-3U (quantity 3)
Battery Access
Front panel battery access door
Battery Replacement Description
Hot-swappable, user replaceable batteries
Expandable Runtime
Yes
Voltage Regulation:
Voltage Regulation Description
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 167 to 260
Overvoltage Correction
Input voltages between 228 and 260 are reduced by 12%
Undervoltage Correction
Input voltages between 167 and 194 are boosted by 12%
User Interface, Alerts & Controls:
Switches
2 Switches control off/on power status and alarm-cancel/self-test operation
Alarm Cancel Operation
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate lowbattery status
Audible Alarm
Audible alarm indicates power-failure, overload and low-battery conditions
LED Indicators
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
Surge / Noise Suppression:
UPS AC Suppression Joule Rating
1020
UPS AC Suppression Response Time
Instantaneous
EMI / RFI AC Noise Suppression
Yes
Physical:
Cooling Method
Fan
Installation Form Factors Supported with Included Accessories
4 post 19 inch rackmount
Installation Form Factors Supported with Optional Accessories
2 post rackmount ( 2POSTRMKITHD ); Tower ( 2-9USTAND )
Minimum Required Rack Depth with External Battery Pack (cm)
81
Minimum Required Rack Depth with External Battery Pack (in.)
32
Minimum Required Rack Depth without External Battery Pack (cm)
76
Minimum Required Rack Depth without External Battery Pack (in.)
30
Primary Form Factor
Rackmount
Primary UPS Depth (mm)
635
Primary UPS Height (mm)
132
Primary UPS Width (mm)
445
Rack Height
3U
Shipping Dimensions (hwd / cm)
30.48 x 58.42 x 83.82
Shipping Dimensions (hwd / in.)
12.00 x 23.00 x 33.00
Shipping Weight (kg)
83.91
Shipping Weight (lbs.)
185.00
UPS Housing Material
Steel
UPS Power Module Dimensions (hwd, cm)
13.21 x 44.45 x 63.50
UPS Power Module Dimensions (hwd, in.)
5.2 x 17.5 x 25
UPS Power Module Weight (kg)
65.00
UPS Power Module Weight (lbs.)
143.3
Environmental:
Operating Temperature Range
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity
5 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load)
366
AC Mode Efficiency Rating (100% Load)
97%
Audible Noise
45 dBA maximum, front side 1m
Communications:
Network Management Cards
SNMPWEBCARD ; TLNETCARD ; WEBCARDLX
Network Monitoring Port Description
Supports detailed monitoring of UPS and site power conditions
PowerAlert Software
For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at [link removed by ]
Communications Cable
USB
WatchDog Compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
Communications Interface
DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB
![Buy Now Buy Now](buy.gif)