Manufacturer: Tripp Lite
Model: Tripp Lite SmartOnline UPS 1500VA 1200W, LCD, RM, 2U, 120V
Condition: New batteries, refurbished UPS
Part Number: SU1500RTXL2UA
Maximum output: 1200W / 1500VA
Typical backup time at half load:14 minutes (600 Watts)
Typical backup time at full load: 5 minutes (1200 Watts)
Warranty: 1 year full replacement warranty
Tripp Lite SmartOnline 1500VA 1200W RM120V SU1500RTXL2UA User's Manual
SU1500RTXL2UA - Tripp Lite SmartOnline 1500VASpecifications:
Input:
Rated input current (Maximum Load)
12A
Nominal Input Voltage(s) Supported
120V AC
UPS Input Connection Type
NEMA 5-15P
Input Circuit Breakers
20A
UPS Input Cord Length (ft.)
10
UPS Input Cord Length (m)
3.1
Recommended Electrical Service
15A 120V
Input Phase
Single-Phase
Input Frequency
50/60Hz +/-5%
Output:
Output Volt Amp Capacity (VA)
1500
Output Capacity (kVA)
1.5
Output Watt Capacity (Watts)
1200
Output kW Capacity (kW)
1.2
Output Capacity Details
OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% load for 3 minutes; 150% load for 30 seconds and >150% load for 0.5 seconds before switching to BYPASS (when bypass input voltage and frequency are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE bypass limits)
Power Factor
0.8
Crest Factor
3:1
Frequency Compatibility
50 / 60 Hz
Frequency Compatibility Details
Output frequency matches input nominal on startup, defaults to 60 Hz on cold-start
Output Voltage Regulation (Line Mode)
+/- 2%
Output Voltage Regulation (Economy Line Mode)
+/- 10%
Output Voltage Regulation (Battery Mode)
+/- 2%
Load Management Receptacles
Two switchable 5-15R load banks (bank 1 - two outlets, bank 2 - four outlets)
Output AC Waveform (AC Mode)
Sine wave
Output AC Waveform (Battery Mode)
Pure Sine wave
Nominal Output Voltage(s) Supported
120V
Output Receptacles
(6) NEMA 5-15R
Individually Controllable Load Banks
Yes
Battery:
Battery Type
Valve Regulated Lead Acid (VRLA)
Full Load Runtime (min.)
5 min. (1200w)
Half Load Runtime (min.)
14 min. (600w)
Expandable Battery Runtime
Extended runtime supported via optional external battery packs
Expandable Runtime
Yes
External Battery Pack Compatibility
BP48V24-2U (limit 1); BP48V60RT-3U (multi-pack compatible); BP48V27- 2US (multi-pack compatible)
DC System Voltage (VDC)
48
Battery Recharge Rate (Included Batteries)
Less than 6 hours from 10% to 80% (typical, full load discharge)
Battery Access
Front panel battery access door
Internal UPS Replacement Battery Cartridge
RBC94-2U
Battery Replacement Description
Hot-swappable, user replaceable batteries
Voltage Regulation:
Voltage Regulation Description
Online, double-conversion power conditioning
Overvoltage Correction
Power-fail alarm can be silenced using alarm-cancel switch
Undervoltage Correction
Voltage boost of 12% applies when input voltage is between 96 and 108
Severe Undervoltage Correction
Voltage boost of 24% applies when input voltage is between 83 and 95
User Interface, Alerts & Controls:
Switches
2 switches control off/on power status and alarm-cancel/self-test operation
Alarm Cancel Operation
Power-fail alarm can be silenced using alarm-cancel switch
Audible Alarm
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
LED Indicators
14 LEDs indicate line power, online mode, economy/bypass mode, on-battery, overload, battery low, replace battery and fault status information; 4-LED meter displays load and battery charge levels; LED panel rotates for viewing in rack/tower formats
Surge / Noise Suppression:
UPS AC Suppression Joule Rating
600
UPS AC Suppression Response Time
Instantaneous
UPS Dataline Suppression
1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet
EMI / RFI AC Noise Suppression
Yes
Physical:
Primary Form Factor
Rackmount
Cooling Method
Fan
Included Mounting Accessory Description
Included 4POSTRAILKIT mounting bracket enables installation in 4 post racks from 20.5 to 36 inches (521 to 914mm)
Installation Form Factors Supported:
4 post 19 inch rackmount & 2 post rack
Installation Form Factors Optional Accessories
2 post rackmount (2POSTRMKITWM); 2-4 post front rail rackmount (UPSHDEARKIT); 4 post rackmount short-depth (4POSTRAILKITWM); Tower (2- 9USTAND); Wallmount (2POSTRMKITWM)
Minimum Required Rack Depth with External Battery Pack (cm)
66
Minimum Required Rack Depth with External Battery Pack (in.)
26
Minimum Required Rack Depth without External Battery Pack (cm)
56
Minimum Required Rack Depth without External Battery Pack (in.)
22
Optional Mounting Accessory Notes
Optional 2-9USTAND enables upright tower UPS placement; 2POSTRMKITWM enables wall-mount and 2-post rackmount installation; 4POSTRAILKITWM enables installation in 4-post short-depth racks from 14.5 to 23.5 inches (368 to 597mm); UPSHDEARKIT enables installation in 2 or 4-post racks using front vertical rails only, without rear support
Primary UPS Depth (mm)
483
Primary UPS Height (mm)
89
Primary UPS Width (mm)
445
Rack Height
2U
Shipping Dimensions (hwd / cm)
23.37 x 59.44 x 49.53
Shipping Dimensions (hwd / in.)
9.20 x 23.40 x 19.50
Shipping Weight (kg)
27.94
Shipping Weight (lbs.)
61.60
UPS Housing Material
Steel
UPS Power Module Dimensions (hwd, cm)
8.89 x 44.45 x 48.26
UPS Power Module Dimensions (hwd, in.)
3.5 x 17.5 x 19
UPS Power Module Weight (kg)
20.00
UPS Power Module Weight (lbs.)
44.1
Environmental:
Operating Temperature Range
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity
0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load)
612
AC Economy Mode BTU / Hr. (Full Load)
216
Battery Mode BTU / Hr. (Full Load)
667
AC Economy Mode Efficiency Rating (100% Load)
95%
Communications:
Network Management Cards
SNMPWEBCARD ; TLNETCARD ; WEBCARDLX ; MODBUSCARD ; RELAYIOCARD - Not included
Network Monitoring Port Description
Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure communications; Economy-mode setting option is available using PowerAlert software and DB9 Serial cable connection OR via select Network Management Card options
PowerAlert Software
For local monitoring via the UPS’s built-in communication ports , download PowerAlert Local software at Cable
USB and DB9 cabling included
WatchDog Compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
Network Management Card Description
Network management card optional
Communications Interface
Contact closure; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB (HID enabled)